-92-
Design & installation Guide For McQuay MDS Multi System
Sequence of vacuum drying
According to the different ambient, vacuum drying has two ways:
Ordinary vacuum drying
Operating sequence:
Connect the pressure gauge with the liquid pipe and gas pipe, then run the vacuum pump for
more than 2 hours to reach the vacuity of -755 mmHg.
After pumping for 2 hours, if the pressure is higher than -755 mmHg, or there is some
moisture, then pump it for 1 more hour.
After 3 hours pumping, if the pressure is still higher than -755 mmHg, please check to see if
there are some air leak gap.
When the pressure is -755mmHg, stop pumping and wait for 1 hour to see if the pressure
change. If the pressure change, that means there are some air leak gaps or there is some
moisture in the pipe.
Notes
Vacuum should be held both in the liquid pipe and the gas pipe at the same time.
Type Max. exhaust volume
Application
Vacuum drying Air discharge
Vacuum pump with lubricant
0.02mmHg
Suitable Suitable
100L/min
10mmHg
Unsuitable Suitable
40L/min
Vacuum pump without lubricant
0.02mmHg
Unsuitable Suitable
50L/min
Type of vacuum pump and the vacuity
-755mmHg
-760
-700
-600
-400
-200
0
Vacuum pump
Ordinary vacuum drying
Vacuum rising pressure
Refrigerant charging
Total for 3hours
Vacuum drying
kg/cm
2
(Barometric pressure)