Page view 41
-42-
Design & installation Guide For McQuay MDS Multi System
Model MDS060AR(220V~/50Hz)
Model MDS060AR(380V/3N~/50Hz)
HP
LP
OV-COMP1
OV-COMP2
OV-COMP3
NEUTRAL
McQuay
B GND
A
AI-IN
NEUTRAL
LIVE
RC
C1
PTC
213L21L1 5L3
6T3 224T22T1
KM
C
S
CM
R
JP2JP1
J2
J1
RY7
RY6RY4 RY5
RY3RY1 RY2
MidLet
OutLet
RTN
C-BTM
LOW-FAN
MID-FAN
HI-FAN
DIG COMP
FIXED COMP
PWMV
4WV
TRAN-H
TRAN-L
InLet
OD TEMP.
CN1
DLT
HP
LP
C3
C2
~
M
~
M
Ambient temperature sensor(TH2)
Air discharge temperature sensor of the digital compressor(TH1)
Coil inlet temperature sensor(TH4)
Coil middle temperature sensor(TH5)
Coil outlet 
temperature sensor(TH6)
Connecting indoor
unit communication
JP1
JP2
OFFOFF
Jumper settingsǖ
J1.7 J1.5
J1.4J1.3J1.2J1.1
J1.6
ONOFF OFF OFFOFFOFF OFF
DIP switch J1 settings:
OFF
DIP switch J2 setting:
J2.6
RC
PTC
LP
HP
FU
PWMV
EXV 4WV
KM
C1-2
Description of components and parts:
Symbol DescriptionSymbol Description
Compressor start-up unit
Four-way valve
Contactor
Capacitor
High pressure switch
Relay
Fuse
Electric expansion valve
Solenoid valve
Low pressure switch
K1-3
Trans-
former
15
13
K3
19
K1
17
K2
18
K3K2K1
N
1087
2
1614
3
4
EXV
12
11
N
5
L
N
FU
KM
PWMV 4WV
Shaft
heater
Compressor
white
white
blue
red
Fan 1 Fan 2
black
white
black
red
blue
brown
orange
red
blue
brown
orange
Return air temperature sensor(TH3)
Surge suppressor
Notes:
1:
-----------
Field wiring
2:
--------------
Factory wiring
3: J2.1~2.5 sets the internetworking control address
4: If the unit connected at the end of the bus,JP1,JP2 is on.
HP
LP
OV-COMP1
OV-COMP2
OV-COMP3
NEUTRAL
B GND
A
AI-IN
NEUTRAL
LIVE
McQuay
RC
C1
JP2JP1
J2
J1
RY7
RY6RY4 RY5
RY3RY1 RY2
MidLet
OutLet
RTN
C-BTM
LOW-FAN
MID-FAN
HI-FAN
DIG COMP
FIXED COMP
PWMV
4WV
TRAN-H
TRAN-L
InLet
OD TEMP.
CN1
DLT
HP
LP
C2
~
M
~
M
~
M
Shaft
heater
Trans-
former
Connecting indoor
unit communication
Ambient temperature sensor(TH2)
Air discharge temperature sensor of the digital compressor(TH1)
Coil inlet temperature sensor(TH4)
Coil middle temperature sensor(TH5)
Coil outlet 
temperature sensor(TH6)
17
18
19
T2
T3T1
OL
23
22
21
20
1
2
L1
K1
K2
K3
K3K2K1
71
81
EXV
16
15
L
12
N
8
7
5
3
DB3A
SRT
N
FU
81
N
KM
PWMV
4WV
71 R
DB3A
S
T
KM
OL
EXV
4WV Four-way valve
RC
DIP switch J2 setting:
J2.6
J1.7J1.5
J1.4J1.3J1.2J1.1
J1.6
JP2JP1
LP
HP
K1-3
OFFONOFFOFFOFF
DIP switch J1 settings:
OFF OFF
OFF OFF OFF
14.0A
OL
Overload setting&Jumper settings:
FU
PWMV
DB3A
KM
C1-2 OL
Description of components and parts:
Symbol DescriptionSymbol Description
Reverse phase-loss protector
Contactor
Capacitor
High pressure switch
Overload protector
Low pressure switchRelay
Digital
compressor
Fan 1 Fan 2
white
black
white
black
Fuse
Electric expansion valve
Solenoid valve
Return air temperature sensor(TH3)
Surge suppressor
Notes:
1:
-----------
Field wiring
2:
--------------
Factory wiring
3: J2.1~2.5 sets the internetworking control address
4: If the unit connected at the end of the bus,JP1,JP2 is on.
yellow
green
red
yellow
green
red
red
blue
brown
orange
red
blue
brown
orange
Page view 41