Design & installation Guide For McQuay MDS Multi System
4.3 Refrigerant Piping Design and Installation
4.3.1 Refrigerant Piping Design ( Including Selection of Refnet Joint )
Capacity combination
The indoor units & outdoor units should have a relationship as follows:
Refrigerant piping limit
Note: the equivalent length is calculated as follows:
One refnet joint equals to 0.5m, one distributor kit equals to 1.0m.
The above table is based on the 8/10HP unit.
50%
indoor units' cap
outdoor units' cap
130%
The max. equivalent length L
The max. equivalent length L from the first refnet joint to the indoor unit L
Refnet of gas side
Refnet of liquid side
Refnet of gas side
Refnet of liquid side
D2D4D2D4
D2
D4D2D4D2D4D2D4D2D4
D2
D4
D1
D1
D1
D3
D3
D3
L2
D3
D3
L1
D1
L3
L4
L6
D1 D1 D1
D2
D4
dabc
e
f
g
h
i
L5
Outdoor unit
Liquid valve
Gas valve
Throttle unit
Indoor unit
The height between outdoor unit and indoor unit H1
Height between indoor
unit and outdoor unit H2
Note:We strongly recommend that the capacity modulation equals to 100%.
Allowable value piping section
Actual length
250m
L
1
+L
2
+ L
i
Piping
Max. length(m)
Actual length 125m
L
1
+L
2
+ L
i
Equivalent length 150m
The length from the first branch to the remotest unit L(m) 40m L
2
+L
3
+ L
i
Height between indoor
Outdoor unit is above 50m -
Height
unit and outdoor unit
Indoor unit is above 40m -
Height between indoor unit and outdoor unit 15m -