Design & installation Guide For McQuay MDS Multi System
Note:
All the wiring should be fixed;
Electric wiring must not touch the refrigerant pipe, compressor and fan motor;
All wiring between indoor unit and outdoor unit should be neoprene copper core, and section area of cable should
be in accordance with above requirements.
2.8 Electric Data
2.8.1 Outdoor Unit MDS
Model
MDS080B/ MDS100B/ MDS120B/ MDS150B/ MDS180B/ MDS200B/
MDS080BR MDS100BR MDS120BR MDS150BR MDS180BR MDS200BR
Power supply 380V /3N /50Hz
Cross section area(mm
2
)
610
Q.T.Y 5
Power
cable
Model
MDS220B/ MDS240B/ MDS260B/ MDS280B/ MDS300B/
MDS220BR MDS240BR MDS260BR MDS280BR MDS300BR
Power supply 380V /3N /50Hz
Cross section area(mm
2
)
10 16
Q.T.Y 5
Power
cable
Model
MDS030A/ MDS040A/ MDS050A/ MDS060A/ MDS050A/ MDS060A/
MDS030AR MDS040AR MDS050AR MDS060AR MDS050AR MDS060AR
Power supply 220V /50Hz 380V /3N /50Hz
Cross section area(mm
2
)
6(2.5) 4(2.5)
Q.T.Y 2(1) 4(1)
Power
cable
2.8.2 Indoor unit MCC
Model MCC008T MCC010T MCC015T MCC018T MCC020T MCC025T MCC030T MCC040T MCC050T MCC060T
Power supply 220V /50Hz
Cross section area(mm
2
)
1.5 2.5
Q.T.Y 3
Power
cable
2.8.3 Indoor unit MCK
Model
MCK010T MCK150T MCK180T MCK020T MCK025T MCK030T MCK040T MCK050T
Power supply 220V /50Hz
Power
Cross sectionarea(mm2)
1.5 2.5
Q.T.Y 3
cable
2.8.4 Indoor unit MDB
Model MDB050T MDB060T
Power supply 220V /50Hz
Power
Cross section area(mm
2
)
2.5
Q.T.Y 3
cable
2.8.5 Indoor unit MCM
Model MCM020T MCM030T MCM050T
Power supply 220V /50Hz
Cross section area(mm
2
)
2.5
Q.T.Y 3
Power
cable
2.8.5 Indoor unit MWM
Model MWM008T MWM010T MWM015T MWM020T MWM025T
Power supply 220V /50Hz
Cross section area(mm
2
)
1.5 2.5
Q.T.Y 3
Power
cable