McQuay MWM Specifications Page 56

  • Download
  • Add to my manuals
  • Print
  • Page
    / 90
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 55
54
MWM-J_(ii) Performance Data
Model: M5WM25JR - M5LC25CRJ
Heating Mode
ID DB°C
Outdoor WB°C
-9 -6 -5 6 12 15 18
Q (kW) SC (kW) Q (kW) SC (kW) Q (kW) SC (kW) Q (kW) SC (kW) Q (kW) SC (kW) Q (kW) SC (kW) Q (kW) SC (kW)
15 3z.721 3.721 4.211 4.211 4.375 4.375 6.173 6.173 7.154 7.154 7.645 7.645 8.135 8.135
17 3.623 3.623 3.734 3.734 4.282 4.282 6.166 6.166 7.081 7.081 7.575 7.575 8.069 8.069
19 3.526 3.526 3.257 3.257 4.189 4.189 6.158 6.158 7.008 7.008 7.505 7.505 8.003 8.003
21 3.428 3.428 3.108 3.108 4.096 4.096 6.089 6.089 6.934 6.934 7.435 7.435 7.936 7.936
23 3.331 3.331 3.288 3.288 4.003 4.003 5.956 5.956 6.861 6.861 7.366 7.366 7.870 7.870
25 3.233 3.233 3.467 3.467 3.910 3.910 5.824 5.824 6.788 6.788 7.296 7.296 7.804 7.804
27 3.135 3.135 3.647 3.647 3.817 3.817 5.692 5.692 6.715 6.715 7.226 7.226 7.737 7.737
Remark:
AFR: Air ow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling Capacity (kW)
SHC: Sensible Heat Capacity (kW)
PI: Power Input
Notes:
1. Ratings shown are gross capacities which do not include a deduction for indoor fan motor heat.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 0 °C to 46°C without pressure trip.