McQuay MWM Specifications Page 31

  • Download
  • Add to my manuals
  • Print
  • Page
    / 90
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 30
29
Performance Data MWM-J_(ii)
* Repeat process (a) and (b) in 1
st
step for the
condition below:
(c) Indoor Condition: 25°C DB, 19°C WB
Outdoor Condition: 35°C DB
x
3
= 11.65kW
y
3
= 8.94kW
z
3
= 4.08kW
(d) Indoor Condition: 25°C DB, 19°C WB
Outdoor Condition: 40°C DB
x
4
= 11.36kW
y
4
= 9.03kW
z
4
= 4.43kW
2
nd
Step:
To obtain the Total capacity, Sensible capacity and Power input for
(a) Indoor Condition: 25°C DB, 17°C WB
Outdoor Condition: 35°C DB
Indoor DB˚C Indoor WB˚C
Outdoor DB, ˚C
35
TC (kW) SHC (kW) PI (kW)
........
........
16
25
10.91 10.60 4.00
17
...........................................
x
5
y
5
z
5
19 11.65 8.94 4.08
Total capacity, TC
Interpolation Method:
17º C – 16º C
=
x
5
– 10.91kW
19º C – 16º C 11.65kW – 10.91kW
x
5
= 11.16kW
Sensible capacity, SHC
Interpolation Method:
17º C – 16º C
=
y
5
– 10.60kW
19º C – 16º C 8.94kW – 10.60kW
y
5
= 10.05kW
Power Input, PI
Interpolation Method:
17º C – 16º C
=
z
5
– 4.00kW
19º C – 16º C 4.08kW – 4.00kW
z
5
= 4.03kW
Page view 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 89 90

Comments to this Manuals