McQuay M5WSS Installation Manual Page 36

  • Download
  • Add to my manuals
  • Print
  • Page
    / 216
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 35
Tightening Torque
Use proper torque wrench to tight the flare nuts. If the torque strength is weak, gas leakage may occur. If it is
too tight, the flare nut may crack and it may be non-removable.
Diameter D Torque(Nm)
in mm
1/4 6.35 18
3/8 9.52 42
1/2 12.7 55
5/8 15.88 65
3/4 19.05 100
Vacuuming and Charging
Use a vacuum pump with a back flow preventing adapter to prevent the vacuum pump oil mix with R410A
which will create sludge and damage the equipment. Use only gauge manifold exclusive for R410A for
vacuuming and charging.
a) Gauge Manifold
Gauge Manifold(R410A) Connection Port Size
High Pressure Gauge (Red) -0.1~5.3 Mpa
-76 cm Hg ~ 53 kgf/cm
2
Low Pressure Gauge (Blue) -0.1 ~ 3.8 Mpa
-76 cm Hg ~ 38kgf/cm
2
½ UNF-20
thread per inch
b) Charge Hose
Charge Hose (R410A)
Operating Pressure 5.1 MPa (51 kgf/cm
2
)
Burst Pressure 27.4 MPa (274 kgf/ cm
2
)
Connection Size ½ UNF-20 thread per inch
The different size of connection port from the conventional is to prevent wrong refrigerant charging instead
of R410A.
c) Refrigerant Cylinder
A typical R410A charging cylinder will be identified with the refrigerant name and is coated with pink in
colour as designated by ARI.
R410A is mixture of refrigerant which have different evaporating temperature. So when charging, make sure
only liquid is being withdrawn from the charging cylinder. Charging gas state will affect the performance and
operating condition of the system. Invert the cylinder that does not come with dip pipe during charging.
33
Page view 35
1 2 ... 31 32 33 34 35 36 37 38 39 40 41 ... 215 216

Comments to this Manuals