McQuay M5WSS Installation Manual Page 109

  • Download
  • Add to my manuals
  • Print
  • Page
    / 216
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 108
M5CCWS010CR/M5WSS010AR
Cooling Only/ Cooling Mode (Heatpump)
Water Flow Rate = 0.31 m
3
/hr
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 25 30 35 40 45
TC 2.90 2.78 2.69 2.60 2.46 2.31 2.17
SC 2.84 2.73 2.64 2.56 2.43 2.30 2.17
TC
3.01 2.88 2.78 2.69 2.53 2.37 2.21
SC 2.60 2.52 2.45 2.39 2.30 2.20 2.10
TC
3.16 3.01 2.91 2.80 2.62 2.44 2.26
SC 2.29 2.23 2.20 1.99 2.11 2.06 2.02
TC 3.19 3.06 2.97 2.88 2.71 2.54 2.37
SC
2.10 2.05 2.02 1.98 1.94 1.89 1.85
TC 3.30 3.22 3.16 3.10 2.96 2.82 2.69
SC
1.55 1.52 1.49 1.47 1.43 1.39 1.35
TC 3.34 3.27 3.22 3.17 3.05 2.92 2.79
SC
1.37 1.35 1.33 1.31 1.27 1.23 1.20
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 25 30 35 40 45
TC
3.04 2.91 2.81 2.72 2.57 2.42 2.27
SC 2.97 2.85 2.76 2.68 2.54 2.40 2.27
TC 3.15 3.01 2.91 2.81 2.64 2.48 2.31
SC
2.72 2.63 2.57 2.50 2.40 2.30 2.20
TC 3.30 3.15 3.04 2.93 2.74 2.55 2.36
SC
2.39 2.34 2.30 2.08 2.21 2.16 2.11
TC 3.34 3.20 3.11 3.01 2.83 2.65 2.47
SC 2.19 2.14 2.11 2.07 2.02 1.98 1.93
TC
3.45 3.36 3.30 3.24 3.10 2.95 2.81
SC 1.62 1.59 1.56 1.54 1.50 1.46 1.42
TC
3.49 3.42 3.37 3.32 3.19 3.05 2.92
SC 1.43 1.41 1.39 1.37 1.33 1.29 1.25
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 30 35 40 45
TC 3.10 2.97 2.87 2.78 2.62 2.47 2.32
SC 3.04 2.91 2.82 2.74 2.59 2.45 2.31
TC
3.22 3.07 2.97 2.87 2.70 2.53 2.36
SC 2.78 2.69 2.62 2.56 2.45 2.35 2.25
TC
3.37 3.22 3.11 2.99 2.80 2.61 2.41
SC 2.44 2.39 2.35 2.13 2.26 2.20 2.15
TC 3.41 3.27 3.17 3.07 2.89 2.71 2.53
SC
2.24 2.19 2.15 2.12 2.07 2.02 1.97
TC 3.53 3.44 3.37 3.31 3.16 3.02 2.87
SC
1.65 1.62 1.60 1.57 1.53 1.49 1.45
TC 3.56 3.49 3.44 3.39 3.25 3.12 2.98
SC 1.46 1.44 1.42 1.40 1.36 1.32 1.28
23
24
15.5
17
19
20
Entering Water Temperature, (°C)
27.0
15.5
17
19
20
23
24
15.5
17
Entering Water Temperature, (°C)
27.0
Entering Water Temperature, (°C)
27.0
19
20
23
24
Water Flow Rate = 0.51 m
3
/hr
Water Flow Rate = 0.71 m
3
/hr
Note:
1. DB = Dry Bulb, WB = Wet Bulb, TC = Total Capacity, SC = Sensible Capacity
2. All datas above are generated at delta T = Leaving Water Temperature - Entering Water Temperature = 5