Page view 125
M5CKWS050AR/M5WSS050AR
Cooling Only/ Cooling Mode (Heatpump)
Water Flow Rate = 1.53 m
3
/hr
Water Flow Rate = 2.55 m
3
/hr
Water Flow Rate = 3.57 m
3
/hr
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 25 30 35 40 45
TC 14.95 14.31 13.85 13.39 12.65 11.91 11.17
SC 14.63 14.04 13.61 13.19 12.51 11.83 11.16
TC
15.52 14.82 14.33 13.83 13.01 12.19 11.37
SC 13.41 12.96 12.64 12.33 11.82 11.32 10.83
TC
16.27 15.51 14.97 14.43 13.50 12.57 11.64
SC 11.78 11.51 11.32 10.25 10.88 10.62 10.38
TC 16.45 15.77 15.29 14.81 13.94 13.06 12.19
SC
10.80 10.55 10.38 10.21 9.97 9.73 9.50
TC 16.99 16.57 16.26 15.96 15.25 14.54 13.83
SC
7.97 7.81 7.69 7.58 7.38 7.17 6.98
TC 17.18 16.83 16.59 16.34 15.69 15.03 14.38
SC
7.05 6.93 6.84 6.75 6.55 6.36 6.16
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 25 30 35 40 45
TC
15.64 14.96 14.48 14.00 13.23 12.46 11.68
SC 15.30 14.68 14.23 13.79 13.08 12.37 11.67
TC 16.22 15.50 14.98 14.47 13.61 12.75 11.89
SC
14.02 13.55 13.22 12.89 12.36 11.84 11.32
TC 17.01 16.22 15.65 15.09 14.12 13.15 12.17
SC
12.32 12.03 11.84 10.71 11.38 11.11 10.85
TC 17.20 16.50 15.99 15.49 14.57 13.66 12.75
SC 11.30 11.03 10.85 10.68 10.42 10.17 9.94
TC
17.77 17.33 17.01 16.69 15.95 15.21 14.46
SC 8.33 8.16 8.05 7.93 7.71 7.50 7.30
TC
17.96 17.60 17.35 17.09 16.40 15.72 15.04
SC 7.38 7.25 7.15 7.06 6.85 6.65 6.44
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 25 30 35 40 45
TC 15.97 15.29 14.79 14.30 13.51 12.73 11.94
SC 15.63 15.00 14.54 14.09 13.36 12.64 11.92
TC
16.57 15.84 15.31 14.78 13.90 13.03 12.15
SC 14.32 13.84 13.50 13.17 12.63 12.10 11.57
TC
17.38 16.57 15.99 15.42 14.42 13.43 12.44
SC 12.59 12.29 12.09 10.95 11.62 11.35 11.09
TC 17.57 16.85 16.34 15.82 14.89 13.96 13.02
SC
11.54 11.27 11.09 10.91 10.65 10.39 10.15
TC 18.15 17.70 17.37 17.05 16.29 15.53 14.78
SC
8.51 8.34 8.22 8.10 7.88 7.66 7.45
TC 18.35 17.98 17.72 17.46 16.76 16.06 15.36
SC 7.54 7.40 7.31 7.21 7.00 6.79 6.58
Entering Water Temperature, (°C)
27.0
Entering Water Temperature, (°C)
27.0
19
20
23
24
Entering Water Temperature, (°C)
27.0
15.5
17
19
20
23
24
15.5
17
23
24
15.5
17
19
20
Note:
1. DB = Dry Bulb, WB = Wet Bulb, TC = Total Capacity, SC = Sensible Capacity
2. All datas above are generated at delta T = Leaving Water Temperature - Entering Water Temperature = 5
°C
123