Performance Data MWM-J-2011
Model: MWM09JR - MLC09CR
Heating Mode
ID DB°C
Outdoor WB°C
-9 -6 -5 6 12 15 18
TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)
15 1.169 1.169 1.441 1.441 1.532 1.532 2.528 2.528 3.071 3.071 3.343 3.343 3.615 3.615
17 1.145 1.145 1.414 1.414 1.503 1.503 2.523 2.523 2.988 2.988 3.250 3.250 3.512 3.512
19 1.122 1.122 1.386 1.386 1.474 1.474 2.517 2.517 2.904 2.904 3.157 3.157 3.409 3.409
21 1.098 1.098 1.359 1.359 1.445 1.445 2.512 2.512 2.821 2.821 3.064 3.064 3.306 3.306
23 1.090 1.090 1.335 1.335 1.417 1.417 2.386 2.386 2.737 2.737 2.971 2.971 3.204 3.204
25 1.083 1.083 1.312 1.312 1.388 1.388 2.260 2.260 2.654 2.654 2.877 2.877 3.101 3.101
27 1.076 1.076 1.288 1.288 1.359 1.359 2.134 2.134 2.571 2.571 2.784 2.784 2.998 2.998
FROST REGION
Remark:
AFR: Air ow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling Capacity (kW)
SHC: Sensible Heat Capacity (kW)
PI: Power Input
Notes:
1. Ratings shown are gross capacities which do not include a deduction for indoor fan motor heat.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 0 °C to 46°C without pressure trip.