M5LCX-2009DC Inverter Single SplitModels: M5LCX 010 C/CRM5LCX 015 C/CRM5LCX 020 C/CRM5LCX 025 C/CRCatalog
9M5LCX-2009Indoor UnitM5CMXProduct Line-Up G17 G17 (w/o Turbo Mode) 09A-AP 09A-EC Ionizer Filter Saranet Fil
99M5LCX-2009Electrical DataElectrical Data - Cooling Only (With Torque Control) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITH
100M5LCX-2009Electrical DataElectrical Data - Cooling Only 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2)
101M5LCX-2009Electrical DataElectrical Data - Cooling Only 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2)
102M5LCX-2009Electrical DataElectrical Data - Cooling Only 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2)
103M5LCX-2009Wiring DiagramIndoor UnitModel: M5WMX010/015G/GROutdoor UnitModel: M5LCX010/015C/CRWiring Diagram
104M5LCX-2009Indoor UnitModel: M5WMX020/025G/GROutdoor UnitModel: M5LCX020/025C/CRWiring Diagram
105M5LCX-2009Indoor UnitModel: M5CKX020/025A/AROutdoor UnitModel: M5LCX020/025C/CRWiring Diagram
106M5LCX-2009Wiring DiagramIndoor UnitModel: M5CKX010/015C/CROutdoor UnitModel: M5LCX010/015C/CR
107M5LCX-2009Indoor UnitModel: M5CKX020C/CROutdoor UnitModel: M5LCX020C/CRWiring Diagram
108M5LCX-2009Wiring DiagramIndoor UnitModel: M5CMX015E/EROutdoor UnitModel: M5LCX015C/CR
10M5LCX-2009Indoor UnitM5CCXProduct Line-up G17 SLM WIRED 09A-AP 09A-EC Ionizer Filter Saranet Filter
109M5LCX-2009Indoor UnitModel: M5CMX020/025E/EROutdoor UnitModel: M5LCX020/025C/CRWiring Diagram
110M5LCX-2009Indoor UnitModel: M5CCX010/015C/CROutdoor UnitModel: M5LCX010/015C/CRWiring Diagram
111M5LCX-2009Indoor UnitModel: M5CCX020/025C/CROutdoor UnitModel: M5LCX020/025C/CRWiring Diagram
112M5LCX-2009Indoor Air FiltersService Parts Maintenance Procedures Period1.Remove any dust adhering to the filter by using avacuum cleaner or wash in
113M5LCX-2009TroubleshootingTroubleshootingFault ConditionsNo1 The air conditioner unit will not resume afterpower failure.• The air conditioner uni
114M5LCX-2009TroubleshootingBy means of pressure reading: Pressure Data Circuit Too low A little low Normal A little high Too high Probable cause
115M5LCX-2009TroubleshootingBymeansofdiagnosticowchart:Generally, there are two kinds of problems, i.e. starting failure and insufcient cooling
116M5LCX-2009Troubleshootingii ) Diagnosis of Refrigerant Circuit / ApplicationThere might be some causes where the unit starts running but does not p
117M5LCX-2009Troubleshooting119Satisfactory operation with temperature difference of air intake & discharge of indoor unit14°C to 20°C. *( * value
118M5LCX-2009TroubleshootingIndicator LightsIR Signal ReceiverWhen an infrared remote control operating signal has been transmitted, the signal receiv
11M5LCX-2009Outdoor UnitM5LCXProduct Line-upVB2.0LJ DSCAACap TubeEXVGold coatedBlue coatedBareContactorHPLPDC Inverter RotaryDC Inverter ScrollCEDrain
119M5LCX-2009TroubleshootingCompressor Stopped Troubleshooting InstructionsKeep the Main Power Supply ONOpen up the Outdoor Unit’s Top Panel or Servic
120M5LCX-2009Exploded View And Parts ListExploded View And Parts ListINDOOR UNITMODEL : M5WMX010/015G/GR1 Assy. Chassis R501240641512Motor, BlowerR03
121M5LCX-2009INDOOR UNITMODEL : M5WMX020/025G/GR1 Assy. Chassis R501240681702Motor, BlowerR500340747473BlowerR030290291584Bush, FanR110140237755Assy.
122M5LCX-2009INDOOR UNITMODEL : M5CKX020/025A/ARExploded View And Parts List
123M5LCX-2009MODEL : M5CKX020/025A/AR1 Assy. Base Pan R500130287452Motor, FanM5CKX - 020AR03039001735M5CKX - 020ARR03039001735M5CKX - 025AR0303900173
124M5LCX-2009INDOOR UNITMODEL : M5CKX010/015/020C/CRExploded View And Parts List
125M5LCX-2009MODEL : M5CKX010/015/020C/CR1 Assy. Base Pan R500140579062 Assy. Casing R50014057905Side A Panel R01014053369Side B Panel R010140533703A
126M5LCX-2009INDOOR UNITMODEL : M5CMX015/020/025E/ERExploded View And Parts List
127M5LCX-2009MODEL : M5CMX015/020/025E/ER1 Assy. Top Panel R501240749072Assy. Heat ExchangerM5CMX - 015E/ERR50024085233M5CMX - 020E/ERR50024080385M5C
128M5LCX-2009INDOOR UNITMODEL : M5CCX010C/CR1 Cabinet R010130340042Assy. Fan DeckR500140326273Assy. Heat ExchangerR500240793834Assy. Drain PanR500630
12M5LCX-2009Self DiagnosisThe microprocessor provides the possibility to detect and diagnose any fault or malfunction that occurs in the system. The e
129M5LCX-2009INDOOR UNITMODEL : M5CCX015/020/025C/CRExploded View And Parts List
130M5LCX-2009MODEL : M5CCX015/020/025C/CR1 CabinetM5CCX - 015C/CRR01013032453M5CCX - 020C/CRR01013034005M5CCX - 025C/CRR010130323622Assy. Fan DeckM5C
131M5LCX-2009OUTDOOR UNITMODEL : M5LCX010/015C/CR1Assy. Base Pan R500140571902Assy. Outdoor CoilM5LCX - 010CR50024084150M5LCX - 015CR50024084151Assy.
132M5LCX-2009OUTDOOR UNITMODEL : M5LCX020/025C/CR1Assy. Base Pan R500140738302Assy. Outdoor Coil R500240733843CompressorR500490242634Assy. Valve Brac
© 2009 McQuay International +1 (800) 432-1342 www.mcquay.com Products manufactured in an ISO certified facility. This document contains the most c
13M5LCX-2009Application InformationOutdoor temp. (°C DB) Heating CoolingOutdoor temp. (°C WB)Outdoor temp. (°C DB)15 24193546STD-915 2162718STDIndo
14M5LCX-2009Refrigerant Circuit DiagramModel: M5LCX010C/CR-M5WMX010G/GR M5LCX015C/CR-M5WMX015G/GRModel: M5LCX020C/CR-M5WMX020G/GR M5L
15M5LCX-2009Model: M5LCX020C/CR-M5CKX020A/AR M5LCX025C/CR-M5CKX025A/AR M5LCX025C/CR-M5CKX020C/CRModel: M5LCX010C-M5CKX010C M5LCX01
16M5LCX-2009Model: M5LCX020C-M5CMX020E M5LCX025C-M5CMX025E Model: M5LCX020CR-M5CMX020ER M5LCX025CR-M5CMX025ER A
17M5LCX-2009Model: M5LCX020C-M5CMX020E M5LCX025C-M5CMX025E Model: M5LCX010C-M5CCX010C M5LCX015C-M5CCX015C
18M5LCX-2009Application InformationModel: M5LCX020CR-M5CCX020CR M5LCX025CR-M5CCX025CR Model: M5LCX010CR-M5CCX010CR M5LCX015CR-M5CC
M5LCX-2009Table of Contents“McQuay” is a registered trademark of McQuay International. All rights reserved.© 2009 McQuay International. All rights res
19M5LCX-2009Controller G17MODEP1 P2SLEEPSETCANCELON TIMERSETCANCELOFF TIMER612151113147431092185Operation Guide1 Transmission SourceThe source where t
20M5LCX-2009SLM 31 Temperature (Seven Segments) 7 Temperature Setting• To indicate the ambient temperature set by the user.• Set the desired temperat
21M5LCX-2009Installation GuidelineSafety Precautions WARNING CAUTIONInstallation and maintenance should be performed by qualifi ed persons who are fami
22M5LCX-2009Installation DiagramApplication Information
23M5LCX-2009Indoor UnitWall MountedInstall the fan coil (indoor) unit at a location with the following requirements• Location is suitable for wiring,
24M5LCX-2009CAUTION :Drilling Holes And Mounting Plate Installation• Paste the installation plate provided on the desired location on the wall and mar
25M5LCX-2009Application InformationIndoor Unit Preparation• The refrigerant piping can be routed to the unit in 5 directions, by using the cut outs in
26M5LCX-2009Application Information890.0 mm (ceiling board opening)790.0 mm (hanging rod)890.0 mm (ceiling opening)620.5 mm (hanging rod)PipingDirecti
27M5LCX-2009Indoor UnitCeilingBoardUnit HangingDrain Piping WorkNote: This indoor unit use drain pump for condensed water drainage. Install the unit
28M5LCX-2009Panel Installation• The front panel can only be tted in one direction, follow the piping direction. (Follow piping arrow sticker on the f
2M5LCX-2009NomenclatureIndoor UnitM 5 WM X 010 G RBrandM : McQuayModel NameCapacity IndexModel TypeRefrigerant5 : R410AWM : Wall MountedInver
29M5LCX-2009Possible Direction For Air Discharge and Air IntakePossible Opening Dimension for Duct ConnectionShort Duct SpecificationApplication for M
30M5LCX-2009Fresh Air Intake For M5CKX-C UnitTake off the panel from the indoor unitRemove the PE foam from the drain pan and another one on the unit.
31M5LCX-2009Fig. 3Indoor UnitCeiling ConvertiblePreliminary Site Survey• Electrical supply and installation is to confirm to local authority's (
32M5LCX-2009Application InformationFig.4Fig.5Under ceiling typeFloor standing typePlease ensure that the following steps are taken:• Check the gradie
33M5LCX-2009Under Ceiling InstallationInstall the Suspension Bolts1. Install the suspension bolts so that it can support the indoor unit.2. Adjust the
34M5LCX-2009Floor Standing Installation1. Refer to the dimension as illustrated when installing the mounting bracket.2. Determine the pipe hose positi
35M5LCX-2009Piping and Drain Hose InstallationUnder Ceiling Type1. The piping direction can be 2 ways as illustrated.2. The drain hose is only 1 way.O
36M5LCX-2009How to Remove the Air Inlet Grille1. Remove the air inlet grille by both hands as the direction shown.2. Loosen the screws for fixing the
37M5LCX-2009Application Information How to Install the Air FilterTo Adjust the Vane DirectionAdjust the vane linkage as the direction shown to get the
38M5LCX-2009Indoor UnitCeiling ConcealedPreliminary Survey• Electrical supply and installation is to conrm to local authority’s (e.g. National Elect
3M5LCX-2009Indoor UnitM 5 CC X 010 A RBrandM : McQuayModel NameCapacity IndexModel TypeRefrigerant5 : R410ACK : Ceiling CassetteCM : Ceiling
39M5LCX-2009• A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.• A place protected from direct sunlight.
40M5LCX-2009Installation Clearances• Outdoor units must be installed such that there is no short circuit of the hot discharge air or obstruction to s
41M5LCX-2009Condensed Water Disposal Of Outdoor Unit (Heat Pump Unit Only)• There are 2 holes on the base of Outdoor Unit for condensed water to ow
42M5LCX-2009There must be a double pole switch with a minimum 3mm contact gap and fuse/ circuit breaker as recomended in the xed installatio
43M5LCX-2009Always choose the shortest path for refrigerant piping and follow the recommendation as tabulated below:Remarks: The refrigerant pre-charg
44M5LCX-2009Imperial Rigid6.35 / 1/4” 1.3 0.79.52 / 3/8” 1.6 1.012.70 / 1/2” 1.9 1.315.88 / 5/8” 2.2 1.719.05 / 3/4” 2.5 2.0Pipe Ø, D (mm/in)A (mm)C)
45M5LCX-2009Special Precautions for R410ASpecial Precautions When Dealing With Refrigerant R410A Unit(1) What is new refrigerant R410A? R410A is a ne
46M5LCX-2009Vacuuming And ChargingPurging The Piping And The Indoor UnitExcept for the outdoor unit which is pre-charged with refrigerant, t
47M5LCX-2009Additional Charge Per Meter Model R410A M5LCX010/015/020/025C/CR 19.5 g/mThe additional refrigerant charge amount recommended
48M5LCX-2009General Data - Cooling Only1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING
4M5LCX-2009M 5 LC X 010 C RBrandM : McQuayModel NameCapacity IndexModel TypeRefrigerant5 : R410ALC : Single Split Condensing UnitInverter Sys
49M5LCX-20091) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 51
50M5LCX-20091) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 51
51M5LCX-20091) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY
52M5LCX-20091) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY
53M5LCX-2009General Data - Heat pump (With Torque Control)1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
54M5LCX-20091) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 51
55M5LCX-20091) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 51
56M5LCX-20091) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 51
57M5LCX-2009General Data - Heat pump1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE
58M5LCX-2009General Data - Heat pump1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE
5M5LCX-2009Product Line-UpIndoor UnitM5WMXG17VA2.0Ionizer FilterSaranet FilterNegative IonizerNano Technology Air FiltrationO2 TherapyNon-Thermal Plas
59M5LCX-20091) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY
60M5LCX-20091) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 51
61M5LCX-20091) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 51
62M5LCX-20091) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY
63M5LCX-20091) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY
64M5LCX-20091) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 51
65M5LCX-20091) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 51
66M5LCX-20091) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY
67M5LCX-20091) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY
68M5LCX-2009Components Data - Cooling Only 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. M5WMX
6M5LCX-2009Indoor UnitM5CKX-AG17090A-APIonizer FilterSaranet FilterNegative IonizerNano Technology Air FiltrationO2 TherapyNon-Thermal Plasma (NTP)CEw
69M5LCX-2009Components Data - Cooling Only 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. M5WMX
70M5LCX-2009Components Data - Cooling Only (with Torque Control) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR
71M5LCX-2009Components Data - Heat pump 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. M5WMX010GR M5W
72M5LCX-2009Components Data - Heat pump 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. M5WMX020G
73M5LCX-2009Components Data - Heat pump (with Torque Control) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTI
74M5LCX-2009Components Data - Cooling only 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. M5CKX02
75M5LCX-2009Components Data - Cooling only 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. M5CKX01
76M5LCX-2009Components Data - Cooling only 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. M5CKX02
77M5LCX-2009Components Data - Heat pump 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. M5CKX020AR M5
78M5LCX-2009Components Data - Heat pump 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. M5CKX010CR M5
7M5LCX-2009G17090A-APIonizer FilterSaranet FilterNegative IonizerNano Technology Air FiltrationO2 TherapyNon-Thermal Plasma (NTP)CEwith Cape Tube010C0
79M5LCX-2009Components Data - Heat pump 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. M5CKX020CRM5L
80M5LCX-2009Components Data - Cooling only1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.* WITH TORQUE CONTROL
81M5LCX-2009Components Data - Cooling Only1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.M5CMX020E M5CMX025EM5
82M5LCX-2009Components Data - Heat pump1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.* WITH TORQUE CONTROL
83M5LCX-2009Components Data - Heat pump1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. M5CMX020ER M5CM
84M5LCX-2009Components Data - Cooling only1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. M5CCX010CM5C
85M5LCX-2009Components Data - Cooling only1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. M5CCX020C M5
86M5LCX-2009Components Data - Heat pump1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. M5CCX010CR M5CC
87M5LCX-2009M5CCX020CR M5CCX025CRM5LCX020CR M5LCX025CRBLOWER WHEEL BLOWER WHEEL2 2GALVANISED STEEL GALVANISED STEELDIRECT DIRECTmm/in160 / 6.3 160 / 6
88M5LCX-2009Outline and Dimensionmm ni noisnemiD :etoNOutdoor Unitmm ni noisnemiD :etoNOutdoor UnitModel: M5LCX020/025C/CRModel: M5LCX010/015C/CRMODEL
8M5LCX-2009Indoor UnitPLCKX G17 G18 CE with Auto Air Swing Auto RestartPLCKXA-G17X X XPLCKXC-G17X X XPLCKXCR-G17X X
89M5LCX-2009mm ni noisnemiD :etoNIndoor Unitmm ni noisnemiD :etoNIndoor UnitModel: M5WMX020/025G/GRModel: M5WMX010/015G/GRMODEL A B C D E F G H I J K
90M5LCX-2009Outline and DimensionIndoor UnitModel: M5CKX020/025A/AR, M5CKX010/015/020C/CRIndoor UnitModel: M5CMX015/020/025E/ER MODEL
91M5LCX-2009Indoor UnitModel: M5CCX010/015/020/025C/CRmm ni noisnemiD :etoNA B C D E F G H
92M5LCX-2009Electrical Data - Cooling Only1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEIN
93M5LCX-2009Electrical DataElectrical Data - Cooling Only (With Torque Control)1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHO
94M5LCX-2009Electrical DataElectrical Data - Cooling Only 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) AL
95M5LCX-2009Electrical DataElectrical Data - Cooling Only 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) AL
96M5LCX-2009Electrical DataElectrical Data - Cooling Only 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) AL
97M5LCX-2009Electrical DataElectrical Data - Cooling Only 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) AL
98M5LCX-2009Electrical DataElectrical Data - Cooling Only 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) AL