McQuay WMC Installation Manual

Browse online or download Installation Manual for Small kitchen appliances McQuay WMC. McQuay WMC Installation manual User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Model WMC-145SBS to 400DBS

Installation Manual IM 1029-2 Group: Chiller Part Number: 331374611 00 Effective: October 2012 Supersedes: May 2012 Magnitude™ Magnetic Bearing

Page 2 - Table of Contents

10 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Mounting/Lifting/Total Weights Drawings are for reference only and are not in

Page 3 - W M C 290 D BS

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 11 Chiller Dimensions Figure 5, WMC 145S, 2 Pass (See page 17 for notes.) 6.215

Page 4 - Installation

12 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Figure 6, WMC 145D, 2 Pass (See page 17 for notes.)

Page 5 - Location and Mounting

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 13 Figure 7, WMC 150D, 2-Pass (See page 17 for notes.)

Page 6 - Filtering and Treatment

14 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Figure 8, WMC 250D, 2-Pass (See page 17 for notes.)

Page 7 - Condenser Water Temperature

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 15 Figure 9, WMC 290D, 2-Pass (See page 17 for notes.)

Page 8 - Field Insulation

16 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Figure 10, WMC 400D, 2-Pass (See page 17 for notes.)

Page 9 - Physical Data and Weights

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 17 Drawing Notes NOTES: 1. All dimensions are in inches and [millimeters] unles

Page 10 - 332834901

18 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Pressure Drop Curves NOTE: The Evaporator and Condenser Model Codes are shown

Page 11 - WMC145SBS

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 19 Figure 13, 2-Pass Evaporators WMC Evap - Water Side Pressure Drop(2 pass)010

Page 12

2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Table of Contents Introduction ... 3 N

Page 13

20 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Figure 15, 3-Pass Evaporators WMC Evap - Water Side Pressure Drop(3 pass)0102

Page 14

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 21 Relief Valves As a safety precaution and to meet code requirements, each chi

Page 15

22 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Sizing Vent Piping (ASHRAE Method) Relief valve pipe sizing is based on the d

Page 16

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 23 Electrical Information Wiring, fuse and wire size must be in accordance with

Page 17 - Harmonic Filter Dimensions

24 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Case 2, WMC 145D – 400D Field Power Wiring Case 2 adds optional factory-mount

Page 18 - (1 pass)

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 25 Case 3, WMC 250D, 290D, 400D Field Power Wiring Case 3 adds the combo harmon

Page 19 - Figure 14, 2-Pass Condensers

26 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Case 4, WMC 250D, 290D, 400D Field Power Wiring Case 4 adds both the EMI filt

Page 20 - (3 pass)

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 27 Case 5, WMC 145D – 150D Field Power Wiring Case 5 adds remote-mounted combo h

Page 21 - Relief Valves

28 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Case 6, WMC 145D – 150D Field Power Wiring Refer to Case 5. Case 6 merely add

Page 22 - Common Piping

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 29 Figure 24, Case 8 WMC 145S Field Power Wiring NOTES: 1. Not applicable 2. R

Page 23 - Electrical Information

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 3 Introduction General Description The Daikin McQuay Magnitude™ Frictionless Cen

Page 24

30 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Optional Harmonic Filter The optional harmonic filters are field mounted and

Page 25

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 31 Electrical Data General Note: The RLA for use in the following tables is obta

Page 26

32 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 [Amp] [Amp] 100 to 104 132 1 125 to 130 225 Amps 200 N/A 3 3 GA 105 to 111 1

Page 27

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 33 Table 10, WMC 145D-B & WMC 150D-B, 3/60/460 (Continued) MULTI-POINT CONN

Page 28

34 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Table 12, WMC 145D-B & WMC 150D-B, 3/50/400 SINGLE POINT CONNECTION, STAN

Page 29

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 35 WMC 250D & 290D, Dual Compressor Table 13, WMC 250D-B & WMC 290D-B, 3

Page 30

36 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Table 14, WMC 250D-B & WMC 290D-B, 3/50/400 SINGLE POINT CONNECTION, STAN

Page 31 - WMC 145S, Single Compressor

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 37 WMC 400D 3/60/460 ONLY Table 15, WMC 400D-B, 3/60/460 SINGLE POINT CONNECTION

Page 32 - Continued next page

38 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Figure 25, Power Panel (Front End Box) Power Cable Entrance Access Plate

Page 33

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 39 Figure 26, Control Panel Terminal Board TB UTB1 for Field Wiring Connections

Page 34

4 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Installation Receiving and Handling The unit should be inspected immediately a

Page 35

40 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Figure 27, Field Control Wiring Diagram NOTE: Complete notes are on the fol

Page 36

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 41 Field Wiring Diagram Notes 1. COMPRESSOR FRONT END BOX IS FACTORY MOUNTED A

Page 37 - WMC 400D 3/60/460 ONLY

42 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 VFD Line Harmonics Despite their many benefits, care must be taken when apply

Page 38

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 43 As the technology of drives evolves, switching frequencies increase. These i

Page 39 - Figure 26, Control Panel

44 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Multiple Chiller Setup WMC units have their control components factory wired

Page 40

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 45 MicroTech II Operator Interface Touch Screen (OITS) Settings Settings for any

Page 41 - Control Wiring

46 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Prestart System Checklist Yes No N/A Chilled Water Piping complete ...

Page 42 - VFD Line Harmonics

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 47 Long Term Storage This information applies to new units being stored waiting

Page 43 - System Pumps

48 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Operation Operator Responsibilities It is important that the operator become

Page 44 - Multiple Chiller Setup

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 49 Since there are many other factors that can influence performance, systems ma

Page 45 - Operating Sequence

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 5 Location and Mounting Location WMC chillers are intended only for installation

Page 46 - Prestart System Checklist

50 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Transfer Back to Grid Power: Proper transfer from stand-by generator power ba

Page 47 - Long Term Storage

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 51 Connection to Chiller Connection to the chiller for all BAS protocols will be

Page 48 - Operation

52 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2

Page 50 - Building Automation Systems

© McQuay International • www.daikinmcquay • (800) 432-1342 IM 1029-2 (10/12) Daikin McQuay Learning Institute Now that you

Page 51 - Protocols Supported

6 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 !CAUTION Freeze Notice: Neither the evaporator nor the condenser is self-drain

Page 52

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 7 Flow Switch Note: Chiller units must have flow switches for the evaporator and

Page 53

8 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 !CAUTION Tower water treatment is essential for continued e

Page 54

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 9 Physical Data and Weights With positive pressure systems, the pressure varianc