Ennity™ Console Water Source Heat Pumps
1/2 to 1½ Ton
R-410A Models MHC Standard Range & MHW Geothermal Range
Unit Sizes 007-018
People and ideas you can trust.
Page view 0
1 2 3 4 5 6 ... 51 52

Summary of Contents

Page 1 - 1/2 to 1½ Ton

Catalog 1104-6Ennity™ Console Water Source Heat Pumps 1/2 to 1½ TonR-410A Models MHC Standard Range & MHW Geothermal RangeUnit Sizes 007-018Pe

Page 2 - Contents

engineering dataAirow Correction FactorsTable 8: Airflow Correction FactorsPercent of Nominal Airow85 90 95 100 105 110 115Total Cooling Capacity 0.

Page 3 - Model noMenClature

CAT 1104-6 • Ennity Console WSHP 11 www.DaikinApplied.comControls features & oPtionsControl Choices and Added FunctionalityThe control box is

Page 4 - Pumps, You Benet From:

Control features & oPtionsMicroTech® III Unit ControllerThe MicroTech III Unit Controller is a microprocessor-based control board conveniently loc

Page 5

Control features & oPtionsTable 14: MicroTech III Controller Configuration Jumper SettingsBaseboard Description Jumper(s) Jumper Setting FunctionN

Page 6 - Conguration

Control features & oPtionsCAT 1104-6 • Ennity Console WSHP 14 www.DaikinApplied.comI/O Expansion Module The I/O Expansion Module is a factory

Page 7 - Physical Data

Control features & oPtionsTable 16: I/O Expansion Module Jumper SettingsI/O Expansion Description Jumper(s) Jumper Setting ModelCompressor Options

Page 8 - Fan Performance

MicroTech® III Unit Controller with lonWorks or BACnet Communication ModuleEach Daikin Console Water Source Heat Pump can be equipped with a LonWorks

Page 9 - Operating Limits

Control features & oPtionsCAT 1104-6 • Ennity Console WSHP 17 www.DaikinApplied.comFigure 2: Discharge Air Temperature Sensor (DAT) & Ret

Page 10 - Antifreeze Correction Factors

CAT 1104-6 • Ennity Console WSHP 18 www.DaikinApplied.comWater Source Heat Pump SystemsWater source heat pump systems are one of the most efcien

Page 11

aPPliCationsCAT 1104-6 • Ennity Console WSHP 19 www.DaikinApplied.comClosed Loop Geothermal Applications: AHRI 330/ISO 13256-1 “Vertical Closed L

Page 12 - III Unit Controller

CAT 1104-6 • Ennity Console WSHP 2 www.DaikinApplied.comContentsModel Nomenclature ...3Ennity™ Console Water Source Heat

Page 13

aPPliCationsCAT 1104-6 • Ennity Console WSHP 20 www.DaikinApplied.comApplication ConsiderationsTypical Console InstallationUnit LocationThe Conso

Page 14 - I/O Expansion Module

aPPliCationsTypical Cooling and Heating Refrigeration Cycles (For standard heat pump operation only)Figure 9: Cooling Refrigeration CycleWhen the wall

Page 15

aPPliCationsCAT 1104-6 • Ennity Console WSHP 22 www.DaikinApplied.comUnit SelectionAchieving optimal performance with water source heat pump syst

Page 16

CaPaCity dataUnit Size 007EWT (°F)GPMWPDCooling HeatingEAT (°F) LWT TOT SEN kWEEREAT (°F) LWT TOT kW COP201.0 0.675/63Tint = Operation Not Recommended

Page 17 - RAT sensor

CaPaCity dataUnit Size 007 (continued)EWT (°F)GPMWPDCooling HeatingEAT (°F) LWT TOT SEN kWEEREAT (°F) LWT TOT kW COP901.0 0.675/63 107.7 7139 5815 0.5

Page 18 - AHRI 325 / ISO 13256-1

CaPaCity dataUnit Size 009EWT (°F)GPMWPDCooling HeatingEAT (°F) LWT TOT SEN kWEEREAT (°F) LWT TOT kW COP201.1 3.175/63Tint = Operation Not Recommended

Page 19 - Closed Loop Geothermal

CaPaCity dataUnit Size 009 (continued)EWT (°F)GPMWPDCooling HeatingEAT (°F) LWT TOT SEN kWEEREAT (°F) LWT TOT kW COP901.1 3.175/63 109.2 8520 6930 0.6

Page 20 - Application Considerations

CaPaCity dataUnit Size 012EWT (°F)GPMWPDCooling HeatingEAT (°F) LWT TOT SEN kWEEREAT (°F) LWT TOT kW COP201.6 1.675/63Tint = Operation Not Recommended

Page 21 - PPliCations

CaPaCity dataUnit Size 012 (continued)EWT (°F)GPMWPDCooling HeatingEAT (°F) LWT TOT SEN kWEEREAT (°F) LWT TOT kW COP901.6 1.675/63 105.6 10090 7200 0.

Page 22 - Unit Selection

CaPaCity dataUnit Size 015EWT (°F)GPMWPDCooling HeatingEAT (°F) LWT TOT SEN kWEEREAT (°F) LWT TOT kW COP202.0 2.575/63Tint = Operation Not Recommended

Page 23 - Unit Size 007

Model noMenClatureCategory Code Item Code Option Code Designation & Description (Bold-Italic = Standard)Product Category 01 1 W = Water So

Page 24 - Unit Size 007 (continued)

CaPaCity dataUnit Size 015 (continued)EWT (°F)GPMWPDCooling HeatingEAT (°F) LWT TOT SEN kWEEREAT (°F) LWT TOT kW COP902.0 2.575/63 106.7 13760 10180 0

Page 25 - Unit Size 009

CaPaCity dataUnit Size 018EWT (°F)GPMWPDCooling HeatingEAT (°F) LWT TOT SEN kWEEREAT (°F) LWT TOT kW COP202.4 3.675/63Tint = Operation Not Recommended

Page 26 - Unit Size 009 (continued)

CAT 1104-6 • Ennity Console WSHP 32 www.DaikinApplied.comCaPaCity dataUnit Size 018 (continued)EWT (°F)GPMWPDCooling HeatingEAT (°F) LWT TOT SEN

Page 27 - Unit Size 012

CAT 1104-6 • Ennity Console WSHP 33 www.DaikinApplied.comdiMensional dataSlope Top Unit – High Sill, Right Hand Piping – Unit Size 007 - 012Top V

Page 28 - Unit Size 012 (continued)

CAT 1104-6 • Ennity Console WSHP 34 www.DaikinApplied.comdiMensional dataSlope Top Unit – Low Sill, Right Hand Piping – Unit Size 007 - 012Note:

Page 29 - Unit Size 015

CAT 1104-6 • Ennity Console WSHP 35 www.DaikinApplied.comdiMensional dataSlope Top Unit – High Sill, Right Hand Piping – Unit Size 015 - 018Note:

Page 30 - Unit Size 015 (continued)

CAT 1104-6 • Ennity Console WSHP 36 www.DaikinApplied.comdiMensional dataSlope Top Unit – Low Sill, Right Hand Piping – Unit Size 015 - 018Note:

Page 31 - Unit Size 018

CAT 1104-6 • Ennity Console WSHP 37 www.DaikinApplied.comUnit & Wall Mounted Thermostats - StandaloneThese easy-to-operate comfort command ce

Page 32 - Unit Size 018 (continued)

CAT 1104-6 • Ennity Console WSHP 38 www.DaikinApplied.comTemperature control range: • 45°F to 90°F (7°C to 32°C) Accuracy: ± 1°F (± 0.5°C)Syste

Page 33

CAT 1104-6 • Ennity Console WSHP 39 www.DaikinApplied.comSpecications–668811001Electrical rating: • 24 VAC (18-30 VAC)• 1 amp maximum per term

Page 34

enfinity™ Console Water sourCe Heat PuMPsCAT 1104-6 • Ennity Console WSHP 4 www.DaikinApplied.comIntroductionMore than 30 years ago, McQuay (A me

Page 35

CAT 1104-6 • Ennity Console WSHP 40 www.DaikinApplied.comFigure 15: Optional Water Source Heat Pump Room Temperature Sensor 669529001 WiringMicro

Page 36

CAT 1104-6 • Ennity Console WSHP 41 www.DaikinApplied.comCombination Balancing and Shutoff ValvesConstructed of brass and rated at 400 psig (2758

Page 37 - Standalone

CAT 1104-6 • Ennity Console WSHP 42 www.DaikinApplied.comPiping Packages Dimensions – Left HandFigure 17: Left-Hand, Motorized Valve with Flow Co

Page 38

CAT 1104-6 • Ennity Console WSHP 43 www.DaikinApplied.comPiping Packages Dimensions – Right HandFigure 21: Right-Hand, Motorized Valve with Flow

Page 39 - Pump Room Temperature Sensors

field-installed aCCessories CAT 1104-6 • Ennity Console WSHP 44 www.DaikinApplied.comFigure 26: Motorized Outdoor Air DamperSealSubbaseMotorized

Page 40 - Supply and Return Water Hoses

tyPiCal Wiring diagraMsTypical MicroTech III Unit Controller for Sizes 007-015 – 208/230/60Hz/1-PhaseNotes: Transformer: Unused wire to be capped.2. U

Page 41 - Piping Package (Options)

tyPiCal Wiring diagraMsTypical MicroTech III Unit Controller With Electric Heat for Size 018 208/230/60Hz/1-Phase Table B 208V RED 230V ORGDrawin

Page 42 - 9.81" 7.31"

tyPiCal Wiring diagraMsTypical MicroTech III Unit Controller with Communication Module and Wall-Mounted Room Temperature Sensor – 265/277/60Hz/1-Phase

Page 43 - Outdoor Air Dampers

engineering guide sPeCifiCationsCAT 1104-6 • Ennity Console WSHP 48 www.DaikinApplied.comGeneralContractor shall furnish and install Water Source

Page 44 - Extended End Pocket (Option)

engineering guide sPeCifiCationsPipingThe supply and return lines shall be 5/8" O.D. copper tub-ing and terminate away from the side of the chass

Page 45 - Description

1 Cabinets• Selectable at top or slope top cabinet congurations with multiple grille options, including user congurable, multi-directional grille

Page 46 - 208/230/60Hz/1-Phase

engineering guide sPeCifiCationsCAT 1104-6 • Ennity Console WSHP 50 www.DaikinApplied.comEach communicating unit controller performs the follow-i

Page 47 - Item Description

CAT 1104-6 • Ennity Console WSHP 51 www.DaikinApplied.comOptional Outside Air Damper KitThe damper is located in the back of the subbase for outs

Page 48 - Fan and Motor Assembly

Daikin Applied Training and DevelopmentNow that you have made an investment in modern, efcient Daikin equipment, its care should be a high priority.

Page 49 - Solid-State Control System

design features & oPtionsCAT 1104-6 • Ennity Console WSHP 6 www.DaikinApplied.comCongurationConsole water source heat pumps are available in

Page 50

engineering dataAHRI/ASHRAE/ISO PerformanceTable 1: Performance dataUnitSizeGPM CFMCooling HeatingBtuh/hr Watts EER Btuh/hr Watts COPWater Loop007 1.9

Page 51

engineering dataElectrical DataTable 3: Standard Static MotorUnit SizeVoltage/Hz/PhaseCompressorFan Motor FLATotal Unit FLAMinimum VoltageMinimum Cir

Page 52

engineering dataCAT 1104-6 • Ennity Console WSHP 9 www.DaikinApplied.comInformation for Initial Start-UpStandard Range Units:Units are designed t