ADDITION TO
INSTALLATION AND OPERATION INSTRUCTION
Denmark Dubai USA Brasil Singapore
1A95107NPT 05/2012
FlowCon International assumes no responsibility for mistakes, if any, in any printed material.
DYNAMIC SELF BALANCING
CONTROL VALVE
FlowCon SM with BACnet actuator
- 1 -
FlowCon SM with BACnet actuator
The BACnet PICS document can be
found
at www .flowcon. com. Please see Installation
and Operation Instruction for FlowCon SM
1/2”-1 1/2” or for FlowCon SM 2”-6” to learn
about installation of the valve; fitting and ori-
entation of the actuator; wiring instructions;
basic functions and programming via the
buttons on the actuator
.
Important actuator setup.
At first start-up please make sure to enter the
programming menu and setup/program steps
13 to 16 according to the BACnet system set-
tings. Please note, that the number in step 16
must be unique to the network. The rest of the
setup options can be programmed through
the BACnet connection.
Wiring instructions for the BACnet connection
Black
Red
White
Common
A +
B -
Programming menu (continued).
To enter the programming menu, please
simultaneously press and for 6
seconds, until bottom line blinks. Generally
press to accept value and go to next
step. To change value please press or
keys. Press and simutaneously
for 6 sec. to exit programming menu.
Step Display Description Values
13 Select communication speed.
*scrolling top:
select baud rate
Default: 9600.
Options: 9600, 19200, 38400,
76800.
14 Select MAC address.
*scrolling top:
select mac address
Default: 000.
Options: 000-254.
15 Change of device instance.
*scrolling top:
change device instanc
Default: NO.
Options: YES or NO.
Device instance is changed in
step 16.
16 Select device instance.
*scrolling top:
select device instanc
Default: 0497000.
Change one digit at a time.
Press and to move
between digits.
17 Select out-of-service time-out.
*scrolling top:
out of service in min
Default: 15.
Options: 1-60.
Please re-start actuator for changes
to take effect.
*
*
*
*
*
out of
15
Page view 0
1 2 3 4

Summary of Contents

Page 1 - ADDITION TO

ADDITION TOINSTALLATION AND OPERATION INSTRUCTIONDenmark Dubai USA Brasil Singapore1A95107NPT 05/2012FlowCon International assumes no responsibility

Page 2 - Programming

Denmark Dubai USA Brasil Singapore1A95107NPT 05/2012FlowCon International assumes no responsibility for mistakes, if any, in any printed material.DYN

Page 3 - Condition of the

Denmark Dubai USA Brasil Singapore1A95107NPT 05/2012FlowCon International assumes no responsibility for mistakes, if any, in any printed material.DYN

Page 4 - CONTROL VALVE

Denmark Dubai USA Brasil Singapore1A95107NPT 05/2012FlowCon International assumes no responsibility for mistakes, if any, in any printed material.DYN

Comments to this Manuals

No comments