49
Elevation, m Total Capacity Sensible Capacity
0 1.00 1.00
300 0.99 0.96
600 0.98 0.93
900 0.97 0.90
1200 0.96 0.86
1500 0.94 0.83
1800 0.93 0.80
Heating Capacity Correction Factors
Notes : Adjusted capacity, W (@ Nominal air flow) = base heating capacity (@ nominal 60°C EWT, 21.1°C EAT) x Heating Capacity
Correction Factor
Altitude Correction Factors
EAT
°C 37.8 43.3 45 48.8 54.4 60 65.5 71.1 76.7 82.2 87.7
4.4
0.838 0.980 1.021 1.122 1.265 1.406 1.552 1.698 1.845 1.988 2.134
7.2
0.771 0.913 0.954 1.055 1.198 1.379 1.485 1.631 1.778 1.920 2.067
10.0
0.700 0.843 0.885 0.986 1.130 1.272 1.417 1.563 1.710 1.853 2.000
12.7
0.631 0.773 0.817 0.918 1.062 1.205 1.349 1.495 1.639 1.786 1.931
15.5
0.562 0.705 0.748 0.848 0.992 1.137 1.281 1.427 1.572 1.719 1.865
18.3
0.493 0.636 0.679 0.779 0.923 1.070 1.212 1.358 1.504 1.650 1.799
21.1
0.424 0.567 0.610 0.711 0.855 1.000 1.146 1.290 1.438 1.583 1.730
23.9
0.354 0.498 0.541 0.642 0.786 0.932 1.078 1.222 1.369 1.515 1.664
26.7
0.284 0.428 0.471 0.573 0.717 0.863 1.008 1.155 1.302 1.449 1.597
ENTERING TEMPERATURE, °C