M5ACV-2009Air-Cooled Chiller(R410A Inverter Series)Models: M5ACV 030 CR M5ACV 055 CR M5ACV 075 CR M5ACV 100 CR M5ACV 135 CR M5ACV 210 CRCatalog
3. Hardware Description Legend 3.1 Key Explanation The 2 navigation keys permit item selection and modifying the selected value. E
4. Installation 4.1 Chiller BusChiller NetworkChiller panel needs to be energized with +12Vdc. The 5 way wires that provided is once on the easiest
4.2 Others Configuration • JH2 in chiller panel should let it open (put the jumper header on one pin only) all the time unless us
5. Software Description5.1 IntroductionThe Chiller Panel Controller can be used to control / display the status of Chiller.Status viewing:• ON/OFF sta
5.2 Menu Structures12Status Inverter Chiller Summary Pages Main Menu Unit Selection Menu Operation Menu Settings Menu Timer Menu Alarm Menu Display Me
5.3 Chiller Menu Structure5.3.1 Summary PagesThere are 4 pages in [Summary Pages]. Press UP or DOWN for page scrolling. Press ENTER to go to[Main Menu
5.3.2 Main MenuPress ENTER in [Summary Pages] to go into this menuThere are 5 sub menus in [Main Menu]. Press UP or DOWN to select sub menus, ENTER to
5.3.2.2 Settings MenuSelect [Settings Menu] in [Main Menu] and press ENTER to go into this menu.Some advance settings can be found here. Press UP or D
5.3.2.2.3 Panel OptionSelect [Panel Option] in [Setting Menu] and Press ENTER to go into this menu.User can do some miscellaneous for the panel. These
175.3.2.3 Timer MenuSelect [Timer Menu] in [Main Menu] and press ENTER to go into this menu.All the timer/ schedule settings are included in this menu
Table of ContentsNomenclature ...1- P
5.3.2.3.2 Set DateSelect [Date Setting] in [Timer Menu] and press ENTER to go into this menu.User can set the date in this menu. The date is set accor
5.3.2.4.1 Show AlarmsSelect [Show Alarms] in [Alarm Menu] and press ENTER to go into this menu.User can view all the fault/ alarm records in this menu
5.3.2.5.1 Defrost SensorSelect [Defrost Sensor] in [Display Menu] and press ENTER to go into this menu.User can view the defrost sensor temperature fo
6. Operation User Manual6.1 StartingChiller panel can be set as Master or Slave panel unit. When the Panel ID is set to ‘0’, it acts like a Masterpane
226.2 CHILLER OPERATION CONTROL6.2.1 STARTINGDuring power on for the Chiller Panel, it needs to take several times to collect information from the Chi
6.2.3 Switching On/OffThere are several ways to switch ON/OFF for the Chiller.i) [Summary Pages] Press and hold ON/OFF button (hold 1 second). Pleas
6.2.4 Switching ModeThere are several ways to switch the mode for the Chiller. Please take note that some mode cannot be setdue to current Chiller mod
6.2.5 Changing Mode Set TemperatureThere are 2 ways to change the mode set temperature for the Chiller.i) [Operation Menu]25 <ENTER> <ENTE
6.2.6 Manual DefrostUser can choose which compressor will go into manual defrost cycle by using the Chiller Panel, as longas the condition is fulfille
6.2.7 Advance Parameter SettingsThe Chiller Panel provide user a lot of advance parameter settings for the Chiller. The parameters aredivided into 7
NomenclatureM AC 100 C R-F X AASeries C : C seriesModel Type R : heatpumpOmitted if coolingCapacity
3) Compressor4) Condenser Defrost5) Cool Mode Antifreeze6) Inverter7) Alarm and ContactPlease refer to 8. APPENDIX for detail desciption.28C1 Min Run
6.2.8 Changing PasswordFor security purpose, some places in the panel are password-proctected. User can change the passwordat anytime.User needs to en
6.2.9 Clock SettingUser can set the clock for the panel. Set Time : hh mm 00 : 00 Set Time : yyyy hh mm 2000 /01 / 01 UP or DOWN to change
6.2.11 7 Days Programmable SettingThe are 2 ON/OFF events in one day for the schedule. This schedule is applicable to all the chillers inthe network.U
6.2.12 Viewing Alarm / Erase Alarm RecordWhenever a new fault/ alarm is occurred, there will be a message pop up to show the fault/ alarm.Backlight wi
6.2.13 Viewing Defrost Sensor TemperatureThe Chiller Panel displays defrost sensor temperature for each compressor in [Defrost Sensor]in [Display Menu
6.2.15 Viewing / Clear Compressor Run TimeUser can view/ clear the compressor run time for the Chiller in [Comp Run Time] in [Display Menu].Press UP
* This product must be branded. Screen saver will be deactivated for brand less panel6.3 CMOS Reset• CMOS reset allows user to reset some settings to
Symptoms Possible Cause Troubleshooting1 Panel gets hot - Wiring fault in 12VDC supply - Change a new panel module and turn ON the unit againabnormal
8. Appendix37General Unit Default Min Max ResolutionModel Flag4 0210=Chiller (Chiller+Boiler)1=Heat pump,2=Chiller/ Boiler,3=Heat pump/ Boiler, 4=Chil
M5ACV Product Line-up2Wired handset WCCHGold FinIsolator SwitchTerminal blockScroll compressorCapillary tube (Normal circuit)Capillary tube (Normal
COOL MODE ANTIFREEZE Unit Default Min Max ResolutionA1 Antifreeze heater set-point °C (F) 5 (41) -40 (-40) 40 (104) 1A2 Antifreeze heater differential
Special Precautions When Dealing with Refrigerant R410A Unit1) What is New Refrigerant R410A?R410A is a new HFC refrigerant which does not damage the
d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is toensure that only the original composition of R4
InstallationM5ACV 030/ 055/ 075CR41
M5ACV 030CRM5ACV 055CR / 075CR42
M5ACV 100 / 135 / 210CR43Safety PrecautionsBefore installing the air conditioner unit, please read the following safety precautions carefullyWarning!
CautionPlease take note of the following important points when installing.• Do not install the unit where leakage of flammable gas may occur.If gas l
PPPRESSURE GAUGEGATEVALVEGATEVALVEBALANCINGVALVETHE R MOME TE RFLEXIBLEGATE VALVE (LOWERPOSITION FOR DRAINAGE)AIR VENT (INSTALLHIGHEST POSITION)FAN C
CAUTION Electrical and Wiring• Refer to the wiring diagram provided on the unit when making electrical wiring.• Do not ground any electrical equipment
• All terminals and connection must be tightened.• Avoid any wires from touching the refrigerant pipe. Apply insulation if necessary.• Avoid any wires
Features3True Dual Circuits BPHEThe true dual BPHE puts the secondary circuit (water) in contact with 2 primary circuits (refrigerant). So evenif one
Control Operation GuideThe unit is equipped with a microprocessor controller board. The microprocessor controller is provided togive temperature contr
Sound Data49Sound Pressure LevelOverall125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA)M5ACV030CR 56 60 59 53 48 43 38 59M5ACV055CR 60 63 61 56 52 46 42 6
Selection Pr Selection Pr Selection Pr Selection Pr Selection ProcessocessocessocessocessWater Pressure Drop VS Flow RateModel : M5ACV030CR - Coolin
Water Flow m3/hrPump Head kPaSystem Head kPaAvailable Head Presure kPa2.20 315.00 21.78 293.222.60 300.00 31.81 268.193.00 285.00 41.17 243.833.40 275
52Correction Factors with GLYCOL UseWATER PRESSUREFLOW DROP10 1.015 1.0620 1.04 1.1230 1.08 1.1840 1.135 1.24GLYCOL %LWT/ deg C 10 20 30 40-5 0.89 0.8
Engineering and Physical Data General Data - Heat pump R410A Inverter1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR
General Data - Heat pump R410A Inverter1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING T
General Data - Heat pump R410A Inverter1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING
General Data - Heat pump R410A Inverter1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING
Components Data571) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE
Application InformationRefrigerant Circuit DiagramModel : M5ACV 030CR4M5ACV030CRWater / Refrigerant Circuit DiagramPEXVFILTERILTERILDRIERSUCTIONACCUMU
Components Data1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.58M5ACV100CR M5ACV135CRmm/in600 / 24 660 / 26IP4
Components Data1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.59M5ACV210CRPROPELLER2METALDIRECTmm/in812 / 32IN
Safety Devies1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.601) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.61M5ACV210CRNCOPEN Pa / psi4140 / 600CLOSE Pa / psi3312 / 480NC
Performance DataModel : M5ACV 030CR / 055CR - Cooling62WATER AVAIL. PUMP PUMPCOOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING COOL POWER RU
Model : M5ACV075CR - Cooling63WATER AVAIL. PUMP PUMPCOOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING FLOW HEAD INPUT IN
Model : M5ACV100 / 135CR - Cooling64WATER AVAIL. PUMP PUMPCOOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING FLOW HEAD
Model : M5ACV 210CR - Cooling65WATER AVAIL. PUMP PUMPCOOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING FLOW HEAD INPUT IN
Model : M5ACV 030 / 055CR - Heating66WATER AVAIL. PUMP PUMPHEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPUT
Model : M5ACV 075CR - Heating67WATER AVAIL. PUMP PUMPHEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPUT CURR
FIN TUBEHEAT EXCHANGER(SYSTEM 1)FIN TUBEHEAT EXCHANGER(SYSTEM 2)4-WAY VALVEVARIABLE SPEEDCOMPRESSORCOMPRESSORSUCTIONACCUMULATORSUCTIONACCUMULATORWATER
Model : M5ACV100 / 135CR - Heating68WATER AVAIL. PUMP PUMPHEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPU
Model : M5ACV 210CR - Heating69WATER AVAIL. PUMP PUMPHEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPUT CU
Dimensional DaDimensional DaDimensional DaDimensional DaDimensional DatatatatataModel : M5ACV 030CR701029,015,015,080,6300,079,4406,585,070,5ELECTRIC
Model : M5ACV 075CR71741,4205,8205,815,0592,415,0553,01153,01462,484,0210,0244,0AIR VENT749,6180,01019,670,6265,2510,711433,170,0WAWWTER OUTAAWAWWTER
Model : M5ACV100 / 135CR72F G Model A B C D E Base Leg Hole M5ACV100CR 1500 900 1245 1190 297.5 307.5 1446 M5ACV135CR 1800 1150 1245 1190 347.5 416
Electrical Data Electrical Data - Heat Pump R410A Inverter M5ACV075CRBPOWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50RATED INPUT POWER W 300 x2RATED RUNNING C
Electrical Data - Heat pump R410A InverterM5ACV100CR M5ACV135CRFFPOWER SOURCE V/Ph/HzRATED INPUT POWER W500 1430RATED RUNNING CURRENT A2.2 6.0MOTOR O
Electrical Data - Heat pump R410A Inverter75M5ACV210CRBPOWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50RATED INPUT POWER W820 x2RATED RUNNING CURRENT A3.6 x2M
Wiring DiagramsPAR T NO : 50 13 9 026086 Model : M5ACV 030CR76
77 Model : M5ACV 055CR
FIN TUBEHEAT EXCHANGER(SYSTEM 1)VARIABLE SPEEDCOMPRESSORCOMPRESSORSUCTIONACCUMULATORWATERLIQUIDRECEIVEREXVFILTERDRIERCHECKVALVEEXVCHECKVALVECOMPRESSOR
Model : M5ACV 075CRPAR T NO : 50 13 4 08360278
Model : M5ACV 100/135CR79zH05/HP3/V514N3L2L1LEP1BT ROTALOSIHCTIWSREDWHITEBLACKBLUENTSRABCGA'B'C'ABCGNA'B'C'N'1RTF)
Model : M5ACV 210CRROTALOSIHCTIWS1L3L2LNzH05 / HP3 / V514~083RTSNABCGNA’B’C’1RTF)A05(ABCGNA’B’C’N’2RTF)A52(2 PMOC1 PMOCPMUPUVWUVWUVW5BT4BTREDWHITEBLA
Servicing and MaintenanceServicingServicing or maintenance of these unit must be carried out by experienced personnel with specifictraining in refrige
Troubleshooting82When a malfunction of the unit is detected, immediately switch off the main power supply before proceedingwith the following troubles
Diagnostic flow chart Yes : Faulty : Check : Cause : Remedy No response after power-on Input conditions faulty Is LED main board lit? To check &
No LED on main board normal, but no output. Incorrect output condition Is output condition ok? To check & rectify Yes Is load ok? Incorrect load.
No Water flow error Flow switch faulty or pump stopped Is water flow error persists? To check & rectify Main board faulty Yes To replace Main boa
No Under voltage protection (OV/UN Voltage) Power supply failure Is Power supply > 340VAC? To rectify Power board faulty Yes To replace Power boa
Variable compressor overload (Comp 1 overload) Compressor current & circuit is ok Main board/compressor faulty No To check & replace Restart,
Chiller Panel Controller1. Safety ConsiderationOnly specially trained and technicians and installers are authorized to install and service thisequipm
88Is heat sink temperature >100°C? No IPM Error IPM faulty Is IPM ok? To replace IPM Yes Is current at rated frequency ok? Compressor faulty Is I
89No Variable drive low pressure (Low pressure 1) Low pressure switch faulty Check the Air-Cond. system for low pressure To replace System low pressur
Yes Variable compressor high discharge temperature (Comp 1 discharge overheat) Compressor stops > 110°C? To check & rectify Yes Is Temp. senso
Exploded View and Part ListsModel : M5ACV 030CR91No Description Part no No Description Part no 1 ASSY, BASE PAN R50 01 4 079444 19 COMPENSAT
92Model : M5ACV 055CR1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICENo Description Part no No Description P
93Model : M5ACV 075CRNo Description Part no No Description Part no 1 ASSY, BASE PAN R50 01 4 078737 27 STRUCTURE REAR RIGHT R01 01 4 078641
Model : M5ACV100CR941) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICENO DESCRIPTIONS PART NO NO DESCRIPTIONS PART
Model : M5ACV135CR95NO DESCRIPTIONS PART NO NO DESCRIPTIONS PART NO 1 ASSY, PANEL BASE MAIN R50 01 4 079125 28 PANEL, RIGHT ORIFICE R01 01 4 0
Model : M5ACV210CR96NO DESCRIPTION PART NO NO DESCRIPTION PART NO 1 ASSY, PANEL BASE MAIN R50 01 4 084901 30 ASSY, CONTROL BOX R50 04 4 089239
209© 2009 McQuay International +1 (800) 432-1342 www.mcquay.com Products manufactured in an ISO certified facility.This document contains the most